Euroclass's Cables
Class | Test method(s) | Classification criteria | Additional classification | Aca | EN ISO 1716 | PCS ≤ 2,0 MJ/kg (1) | | B1ca | FIPEC20 Scen 2 (5) And EN 60332-1-2 | FS ≤ 1.75 m and THR1200s ≤ 10 MJ and Peak HRR ≤ 20 kW and FIGRA ≤ 120 Ws-1 H ≤ 425 mm | Smoke production (2, 6) and Flaming droplets/particles (3) and Acidity (4, 8) | B2ca | FIPEC20 Scen 1 (5) and | FS ≤ 1.5 m; and THR1200s ≤ 15 MJ; and Peak HRR ≤ 30 kW; and FIGRA ≤ 150 Ws-1 | Smoke production (2, 7) and Flaming droplets/particles (3) and Acidity (4, 8) | | EN 60332-1-2 | H ≤ 425 mm | Cca | FIPEC20 Scen 1 (5) And | FS ≤ 2.0 m; and THR1200s ≤ 30 MJ; and Peak HRR ≤ 60 kW; and FIGRA ≤ 300 Ws-1 | Smoke production (2, 7) and Flaming droplets/particles (3) and Acidity (4, 8) | | EN 60332-1-2 | H ≤ 425 mm | Dca | FIPEC20 Scen 1 (5) And | THR1200s ≤ 70 MJ; and Peak HRR ≤ 400 kW; and FIGRA ≤ 1300 Ws-1 | Smoke production (2, 7) and Flaming droplets/particles (3) and Acidity (4, 8) | | EN 60332-1-2 | H ≤ 425 mm | | Eca | EN 60332-1-2 | H ≤ 425 mm | | Fca | No performance determined | | |
(1) For the product as a whole, excluding metallic materials, and for any external component (i.e. sheath) of the product. (2) s1 = TSP1200 ≤ 50 m2 and Peak SPR ≤ 0.25 m2/s s1a = s1 and transmittance in accordance with EN 61034-2 ≥ 80% s1b = s1 and transmittance in accordance with EN 61034-2 ≥ 60% < 80% s2 = TSP1200 ≤ 400 m2 and Peak SPR ≤ 1.5 m2/s s3 = not s1 or s2 (3) For FIPEC20 Scenarios 1 and 2: d0 = No flaming droplets/particles within 1200 s; d1 = No flaming droplets/ particles persisting longer than 10 s within 1200 s; d2 = not d0 or d1. (4) EN 50267-2-3: a1 = conductivity < 2.5 μS/mm and pH > 4,3; a2= conductivity < 10 μS/mm and pH > 4.3; a3 = not a1 or a2. No declaration = No Performance Determined. (5) Air flow into chamber shall be set to 8000 ± 800 l/min. FIPEC20 Scenario 1 = prEN 50399-2-1 with mounting and fixing as below FIPEC20 Scenario 2 = prEN 50399-2-2 with mounting and fixing as below (6) The smoke class declared for class B1ca cables must originate from the FIPEC20 Scen 2 test. (7) The smoke class declared for class B2ca, Cca, Dca cables must originate from the FIPEC20 Scen 1 test. (8) Measuring the hazardous properties of gases developed in the event of fire, which compromise the ability of the persons exposed to them to take effective action to accomplish escape, and not describing the toxicity of these gases. |
|
|