Codes and Standards‎ > ‎Industry‎ > ‎Building Codes‎ > ‎Europe‎ > ‎Euroclasses‎ > ‎

Pipe





Class

Test methods(s)

Classification criteria

Additional classification

A1L

EN ISO 1182 (1); And

T ≤ 30°C; and m ≤ 50%; and t= 0 (i.e. no sustained flaming)

-

A2L

EN ISO 1182 (1); Or

T ≤ 50°C; and m ≤ 50%; and tf 20s

--Smoke production(5); and Flaming droplets/ particles (6)

EN ISO 1716; And

PCS ≤ 3.0 MJ.kg-1 (1); and PCS ≤ 4.0 MJ.m-2 (2); and PCS ≤ 4.0 MJ.m-2 (3); and PCS ≤ 3.0 MJ.kg-1 (4)

EN 13823 (SBI)

FIGRA ≤ 270 W.s-1; and LFS < edge of specimen; and THR600s  7.5 MJ

BL

EN 13823 (SBI); And

FIGRA ≤ 270 W.s-1; and LFS < edge of specimen; and THR600s ≤ 7.5 MJ

Smoke production(5); and Flaming droplets/ particles (6)

EN ISO 11925-2(8): Exposure = 30s

Fs ≤ 150mm within 60s

CL

EN 13823 (SBI); And

FIGRA ≤ 460 W.s-1; and LFS < edge of specimen; and THR600s ≤ 15 MJ

Smoke production(5); and Flaming droplets/ particles (6)

EN ISO 11925-2(8): Exposure = 30s

Fs ≤ 150mm within 60s

DL

EN 13823 (SBI); And

FIGRA ≤ 2100 W.s-1

Smoke production(5); and Flaming droplets/ particles (6)

EN ISO 11925-2(8): Exposure = 30s

Fs ≤ 150mm within 60s

EL

EN ISO 11925-2(8): Exposure = 15s

Fs ≤ 150mm within 20s

Flaming droplets/ particles (7)

FL

No performance determined


(*) The treatment of some families of products, e.g. linear products (pipes, ducts, cables etc.), is still under review and may necessitate an amendment to this decision. (1) For homogeneous products and substantial components of non-homogeneous products. (2) For any external non-substantial component of non-homogeneous products. (2a) Alternatively, any external non-substantial component having a PCS ≤ 2.0 MJ.m-2 , provided that the product satisfies the following criteria of EN 13823(SBI) : FIGRA ≤ 20 W.s-1; and LFS < edge of specimen; and THR600s ≤ 4.0 MJ; and s1; and d0. (3) For any internal non-substantial component of non-homogeneous products. (4) For the product as a whole. (5) s1 = SMOGRA ≤ 30m2.s-2 and TSP600s ≤50m2 ; s2 = SMOGRA ≤ 180m2.s-2 and TSP600s ≤ 200m2; s3 = not s1 or s2. (6) d0 = No flaming droplets/ particles in EN13823 (SBI) within 600s; d1 = No flaming droplets/ particles persisting longer than 10s in EN13823 (SBI) within 600s; d2 = not d0 or d1; Ignition of the paper in EN ISO 11925-2 results in a d2 classification. (7) Pass = no ignition of the paper (no classification); Fail = ignition of the paper (d2 classification). (8) Under conditions of surface flame attack and, if appropriate to end–use application of product, edge flame attack.